Technical Data

  • Double rod reinforced tray has a 50mm cable laying depth
  • Standard length of tray is 3m
  • Standard finish is zinc plated
  • No hardware is necessary to connect straight sections
  • For continuous grounding use AF GCLIP

 

Part DescriptionWidth(Nominal)Depth (mm)Weight (kg) (piece)1.5m Span2.0m Span2.5m Span
AF50-100100502.634.223.317.2
AF50-150150503.656.336.627.8
AF50-200200504.258.739.229.8
AF50-300300505.56439.329
AF50-450450508.897.553.939.8
AF50-500500509.5105.46346.5
AF50-6006005010.8114.968.750.7